I posted on here the other day about some suspicious 240v cable and followed the recommendations to replace it. I was already leaning that way but was kind of hoping to be told I was overthinking it. But you all confirmed what I thought. I ran close to 25’ of 10/2 cable from the second story to the basement. Nothing is wired...
I’m an electrician. It is too late but for future reference all new work must be done up to code. An electric dryer requires 10/3 on a 30A breaker that is listed for the panel.
While this is not code compliant, 10/2 will still work but requires you to install the jumper from the neutral to the ground inside the dryer itself.
Fished new wire for the first time! ( kbin.social )
I posted on here the other day about some suspicious 240v cable and followed the recommendations to replace it. I was already leaning that way but was kind of hoping to be told I was overthinking it. But you all confirmed what I thought. I ran close to 25’ of 10/2 cable from the second story to the basement. Nothing is wired...