Fished new wire for the first time! ( kbin.social )

I posted on here the other day about some suspicious 240v cable and followed the recommendations to replace it. I was already leaning that way but was kind of hoping to be told I was overthinking it. But you all confirmed what I thought. I ran close to 25’ of 10/2 cable from the second story to the basement. Nothing is wired yet because it is late and I don’t want to turn on the main breaker.

My step dad let me borrow a 50’ fishing tape and 10’ endoscope which were really helpful. I did not have to cut any walls!

AspieEgg ,

Since you went with 10/2 for a 240v outlet that means your cable will have two hots and a single ground. But the cable you bought will have a black, white and bare/green wire. Make sure that you wrap both ends of the white conductor with red electrical tape to indicate that it is also a hot wire. White normally indicates a neutral, but since you won’t have a neutral wire in this cable, it’s important to mark it. Otherwise someone else may work on this outlet in the future, see a white wire, assume it’s a neutral, wire something up with it as a neutral, and give themselves a pretty bad shock.

Uprise42 OP ,

Yup, I already have the electrical tape to mark it. Though I was told I could mark it red or black and both are universal markings for hot wire. Is that wrong? It doesn’t matter here because I have red tape but for future reference it would be good to know

AspieEgg ,

You can mark it either red or black, but you already have one black wire, so it would be best to mark it red, just to differentiate it.

Switorik ,

I’m an electrician. It is too late but for future reference all new work must be done up to code. An electric dryer requires 10/3 on a 30A breaker that is listed for the panel.

While this is not code compliant, 10/2 will still work but requires you to install the jumper from the neutral to the ground inside the dryer itself.

Uprise42 OP ,

Ya, I know I need to jump the ground when wiring to power cable for the dryer. I was going to do 10/3 since I had the money for it, but lowes and Home Depot were both sold out when I went to pick it up. Whirlpool told me 10/2 would work so I just went with that in the effort of saving time. New dryer is delivered Tuesday so I want the wiring done before then. The 30a double pole breaker was easy though. Probably the least questionable part of this process

assplode ,

Nice job! 💪💪💪

navigatron ,

Woohoo! Saw your previous post, I’m glad it’s going well! Keep us updated

Shadow ,
@Shadow@lemmy.ca avatar

Yay, non sketchy cable!

Uprise42 OP ,
Uprise42 OP ,
Uiop ,

aha, now I feel smart!